Power issues in water heater

I recently replaced my thermostats and elements in my water heater but it's still not functioning properly. Everything is connected the right way but for some reason I have a constant 120v to my lower element and when the thermostat kicks in I get 240v. When the top element kicks in I still have the 120v to lower element. Any fix or test I can do the figure out the problem?

Update (12/29/2018)

It's a Rheem 71 40d b

Diese Frage beantworten Ich habe das gleiche Problem

Ist dies eine gute Frage?

Bewertung 0

3 Kommentare:

What country do you live in?

von

USA.....illinois

von

Hi @tbone42 ,

What make and model are the thermostats?

von

Einen Kommentar hinzufügen

1 Antwort

The heating elements are wired incorrectly or a thermostat is malfunctioning. It sounds like the bottom element is grounded to the shell somewhere, and whichever power line isn't releasing contact.

This can also happen if one of the power line wires and the neutral wire are crossed.

War diese Antwort hilfreich?

Bewertung 0

3 Kommentare:

Heating elements are wired in correctly and the thermostats are both brand new. I also replaced both heating element 6 months ago.

von

The water heater is also 240v so there is no neutral.

von

If you don't have a neutral wire connected to the water heater, something is finding a neutral connection through the plumbing. This can also happen if you're measuring voltage in reference to ground. If an element has 120 vac across it's two terminals, either a thermostat is malfunctioning or something is not right with the wiring.