Overload alarm lights and sound

My ups, after 5 years of continuous operation shows the overload's light .

I unplugged the PC and I replaced the battery but I have not solved the problem.

Then I opened it to see if there are components that are burned or leak but nothing.

To be sure I replaced the cooling fan but nothing has changed.

Can anyone give me some tips?

Thank you very much.

Beantwortet! View the answer Ich habe das gleiche Problem

Ist dies eine gute Frage?

Punktzahl 4

Kommentare:

Hi, i had the same problem twice...!!!

My battery was ok, everything was ok but

the beep keep going on, for overload...

Both times i fixed doing these steps...

- Turn off the unit

- Flip over the unit

- Open the battery-cap and turn the power on

- Green Light is flashing

- Try Now (with the green light flashing) to disconnect the battery...

- Now it should be ON with the Empty battery light on (Red light)

- Connect again the battery as it is...

Now it should be ok...!!!

Good Luck...

von

Einen Kommentar hinzufügen

MacBook Akku Fix Kits

Ab $69.99

Buy Now

MacBook Akku Fix Kits

Ab $69.99

Buy Now

5 Antworten

Gewählte Lösung

Thanks to all. I have not solved the problem. I replaced the old ups with a new one.

War diese Antwort hilfreich?

Punktzahl 1
Einen Kommentar hinzufügen
Hilfreichste Antwort

Roberto, If it alarms, even with nothing plugged in, then it is possible that one of the MOSFET on your mainboard has failed.

War diese Antwort hilfreich?

Punktzahl 4

Kommentare:

metal–oxide–semiconductor field-effect transistor (MOSFET)

http://en.wikipedia.org/wiki/MOSFET

von

Did you solve the problem? Same problem here, 4 years later..

daigoph@gmail.com

von

Einen Kommentar hinzufügen

Hi, i had the same problem twice...!!!

My battery was ok, everything was ok but

the beep keep going on, for overload...

Both times i fixed doing these steps...

- Turn off the unit

- Flip over the unit

- Open the battery-cap and turn the power on

- Green Light is flashing

- Try Now (with the green light flashing) to disconnect the battery...

- Now it should be ON with the Empty battery light on (Red light)

- Connect again the battery as it is...

Now it should be ok...!!!

Good Luck...

War diese Antwort hilfreich?

Punktzahl 2

Kommentare:

Thank you but I replaced the old ups with a new one. Yours sincerely.

von

Einen Kommentar hinzufügen

I too facing the same problem....battery charging process is fine...but when i turn on the inverter it trips and shows overload and keep continuosly beep beeps....pls help me to solve this problem....i expecting board level service suggestions ...thank you

War diese Antwort hilfreich?

Punktzahl 1
Einen Kommentar hinzufügen

My problem solved with removing the all cables also power cable wait 5 minute & connect cable again it's working.

War diese Antwort hilfreich?

Punktzahl 0
Einen Kommentar hinzufügen

Antwort hinzufügen

Roberto wird auf ewig dankbar sein.
Statistik anzeigen:

Letzte 24 Stunden: 20

Letzte 7 Tage: 123

Letzte 30 Tage: 585

Insgesamt: 25,574