Zum Hauptinhalt wechseln

Carrier Grade Updates for Dell PowerEdge R720, R620, and R420XR Systems

Technical reference 4 Seiten · 102.08 KB · PDF

Carrier Grade Updates for Dell PowerEdge R720, R620, and R420XR Systems

Important Information

Image

△!

WARNING: The intra-building port(s) of the equipment or subassembly is suitable for connection to intra-building or unexposed wiring or cabling only. The intra-building port(s) of the equipment or subassembly must not be metallically connected to interfaces that connect to the Outside Plant (OSP) or its wiring. These interfaces are designed for use as intra-building interfaces only (Type 2 or Type 4 ports as described in GR-1089-CORE, Issue 5) and require isolation from the exposed OSP cabling. The addition of Primary Protectors do not provide sufficient protection to connect these interfaces metallically to the OSP wiring.

Image

△!

WARNING: The intra-building port(s) of the equipment or subassembly must have shielded intra-building cabling or wiring that is grounded at both ends.

Network equipment — Includes standard PCIe based Network Interface Card (NIC) and Fibre Channel (FC) devices.

Bonding network — Equipment is suitable for Common Bonding Networks (CBNs).

  • Suitable installation location — Equipment is suitable for installation in Network Telecommunications Facilities (NTF), and locations where the National Electrical Code (NEC) is applicable.

• DC bonding —